| Assessment Year | 2017 |
|---|---|
| Principal Product | Pharmaceuticals |
| NAICS | 325412: Pharmaceutical Preparation Manufacturing |
| SIC | 2834: Pharmaceutical Preparations |
| Sales Range | $1 M to 5M |
| # of Employees | 616 |
| Plant Area |
200,000
ft2
|
| Annual Production | 175,000,000
units
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,526,414 | 28,567,224 |
kWh
|
$0.053 |
| Electricity Demand | $120,844 | 55,121 |
kW-mo/yr
|
$2.19 |
| Electricity Fees | $79,380 | - |
|
- |
| Natural Gas | $569,894 | 147,778 |
MMBtu
|
$3.86 |
| TOTAL YEARLY COSTS | $2,296,532 | |||
| RECOMMENDED SAVINGS* | $574,772 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $139,316 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,762 | $1,000 |
$7,191
135,677
kWh
|
$571
-
kW-mo/yr
|
- | - | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,930 | $8,000 |
$10,127
191,070
kWh
|
$803
-
kW-mo/yr
|
- | - | |
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,156 | $8,000 |
$8,482
160,036
kWh
|
$674
-
kW-mo/yr
|
- | - | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,373 | $5,300 |
$4,051
76,428
kWh
|
$322
-
kW-mo/yr
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $61,512 | $97,637 |
$56,983
1,075,152
kWh
|
$4,529
-
kW-mo/yr
|
- | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $46,572 | $108,715 |
$43,145
814,058
kWh
|
$3,427
-
kW-mo/yr
|
- | - | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,458 | $8,500 |
$3,213
60,613
kWh
|
$245
-
kW-mo/yr
|
- | - | |
| 08 | 2.4221: Install compressor air intakes in coolest locations | $2,903 | $9,500 |
$2,640
49,807
kWh
|
$263
-
kW-mo/yr
|
- | - | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,710 | $37,500 |
$9,922
187,200
kWh
|
$788
-
kW-mo/yr
|
- | - | |
| 10 | 2.7232: Replace existing hvac unit with high efficiency model | $385,040 | $1,360,000 |
$230,708
4,352,980
kWh
|
$18,332
-
kW-mo/yr
|
- | $136,000 | |
| 11 | 2.2441: Preheat boiler makeup water with waste process heat | $8,886 | $32,000 | - | - |
$8,886
-
MMBtu
|
- | |
| 12 | 2.4226: Use / purchase optimum sized compressor | $14,690 | $63,000 |
$12,255
231,230
kWh
|
$2,435
-
kW-mo/yr
|
- | - | |
| 13 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,256 | $10,938 |
$2,026
38,220
kWh
|
$230
-
kW-mo/yr
|
- | - | |
| 14 | 2.4226: Use / purchase optimum sized compressor | $6,524 | $32,000 |
$5,442
102,685
kWh
|
$1,082
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $574,772 | $1,782,090 |
$396,185
7,475,156
kWh
|
$33,701
-
kW-mo/yr
|
$8,886
-
MMBtu
|
$136,000 | ||
| TOTAL IMPLEMENTED | $139,316 | $313,290 |
$127,042
2,397,022
kWh
|
$12,274
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs