Assessment Year | 2017 |
---|---|
Principal Product | Printed Materials |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2754: Commercial Printing, Gravure |
Sales Range | $500 k to 1M |
# of Employees | 31 |
Plant Area |
86,000
ft2
|
Annual Production | 164,000
thousand feet
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $253,160 | 4,132,349 |
kWh
|
$0.061 |
Electricity Demand | $42,132 | 10,739 |
kW-mo/yr
|
$3.92 |
Electricity Fees | $47,590 | - |
|
- |
Natural Gas | $116,780 | 32,107 |
MMBtu
|
$3.64 |
TOTAL YEARLY COSTS | $459,662 | |||
RECOMMENDED SAVINGS* | $25,700 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,149 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,716 | $1,000 |
$6,751
110,702
kWh
|
$965
-
kW-mo/yr
|
- | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $8,680 | $5,000 | - | - |
$8,680
-
MMBtu
|
|
03 | 2.4221: Install compressor air intakes in coolest locations | $1,763 | $2,250 |
$1,481
24,281
kWh
|
$282
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,887 | $7,663 |
$3,279
53,747
kWh
|
$608
-
kW-mo/yr
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,108 | $5,000 |
$1,845
30,258
kWh
|
$263
-
kW-mo/yr
|
- | |
06 | 2.4133: Use most efficient type of electric motors | $1,186 | $5,500 |
$1,002
16,430
kWh
|
$184
-
kW-mo/yr
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $360 | $1,800 |
$305
4,992
kWh
|
$55
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $25,700 | $28,213 |
$14,663
240,410
kWh
|
$2,357
-
kW-mo/yr
|
$8,680
-
MMBtu
|
||
TOTAL IMPLEMENTED | $13,149 | $15,963 |
$11,337
185,871
kWh
|
$1,812
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs