Assessment Year | 2017 |
---|---|
Principal Product | Plastic Bottles |
NAICS | 326160: Plastics Bottle Manufacturing |
SIC | 3085: Plastics Bottles |
Sales Range | $50 M to 100M |
# of Employees | 20 |
Plant Area |
122,000
ft2
|
Annual Production | 862,000,000
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $4,155,040 | 44,754,441 |
kWh
|
$0.093 |
Electricity Demand | $386,725 | 73,673 |
kW-mo/yr
|
$5.25 |
Electricity Fees | $21,659 | - |
|
- |
Natural Gas | $38,491 | 7,741 |
MMBtu
|
$4.97 |
TOTAL YEARLY COSTS | $4,601,915 | |||
RECOMMENDED SAVINGS* | $526,311 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $301,318 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4226: Use / purchase optimum sized compressor | $14,163 | $17 |
$13,334
143,375
kWh
|
$830
-
kW-mo/yr
|
- | |
02 | 2.6212: Turn off equipment during breaks, reduce operating time | $97,167 | $5,000 |
$88,893
955,835
kWh
|
$8,274
-
kW-mo/yr
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $21,749 | $3,000 |
$19,827
213,197
kWh
|
$1,922
-
kW-mo/yr
|
- | |
04 | 2.2437: Recover waste heat from equipment | $41,418 | $13,000 |
$38,998
419,328
kWh
|
$2,420
-
kW-mo/yr
|
- | |
05 | 2.4226: Use / purchase optimum sized compressor | $55,847 | $28,000 |
$52,587
565,451
kWh
|
$3,260
-
kW-mo/yr
|
- | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $128,735 | $65,000 |
$121,217
1,303,412
kWh
|
$7,518
-
kW-mo/yr
|
- | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $40,410 | $26,250 |
$37,502
403,243
kWh
|
$2,909
-
kW-mo/yr
|
- | |
08 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $86,307 | $68,000 |
$79,939
859,554
kWh
|
$6,368
-
kW-mo/yr
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,392 | $38,954 |
$20,781
223,449
kWh
|
$1,612
-
kW-mo/yr
|
- | |
10 | 2.7232: Replace existing hvac unit with high efficiency model | $14,063 | $56,424 |
$12,745
137,046
kWh
|
$1,318
-
kW-mo/yr
|
- | |
11 | 2.7233: Use properly designed and sized hvac equipment | $4,060 | $20,000 | - | - |
$4,060
-
MMBtu
|
|
TOTAL RECOMMENDED | $526,311 | $323,645 |
$485,821
5,223,890
kWh
|
$36,429
-
kW-mo/yr
|
$4,060
-
MMBtu
|
||
TOTAL IMPLEMENTED | $301,318 | $204,395 |
$274,515
2,951,784
kWh
|
$22,742
-
kW-mo/yr
|
$4,060
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs