| Assessment Year | 2017 |
|---|---|
| Principal Product | Perforated Metal |
| NAICS | 332119: Metal Crown, Closure, and Other Metal Stamping (except Automotive) |
| SIC | 3444: Sheet Metal Work |
| Sales Range | $1 M to 5M |
| # of Employees | 40 |
| Plant Area |
135,000
ft2
|
| Annual Production | 1,000,000
units
|
| Production Hrs. Annual | 6,968
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $248,440 | 3,891,600 |
kWh
|
$0.064 |
| Electricity Demand | $24,737 | 9,870 |
kW-mo/yr
|
$2.51 |
| Electricity Fees | $26,217 | - |
|
- |
| Natural Gas | $40,240 | 7,300 |
MMBtu
|
$5.51 |
| TOTAL YEARLY COSTS | $339,634 | |||
| RECOMMENDED SAVINGS* | $72,572 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $24,402 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,786 | $1,000 |
$5,229
81,718
kWh
|
$557
-
kW-mo/yr
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,929 | $15,805 |
$14,045
219,458
kWh
|
$884
-
kW-mo/yr
|
- | |
| 03 | 2.6212: Turn off equipment during breaks, reduce operating time | $6,297 | $7,000 |
$5,679
88,737
kWh
|
$618
-
kW-mo/yr
|
- | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,174 | $3,600 |
$2,928
45,744
kWh
|
$246
-
kW-mo/yr
|
- | |
| 05 | 2.7233: Use properly designed and sized hvac equipment | $23,395 | $32,000 | - | - |
$23,395
-
MMBtu
|
|
| 06 | 2.4226: Use / purchase optimum sized compressor | $2,358 | $7,000 |
$3,168
49,504
kWh
|
- |
$(-810.0)
-
MMBtu
|
|
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $513 | $1,683 |
$423
6,612
kWh
|
$90
-
kW-mo/yr
|
- | |
| 08 | 2.4226: Use / purchase optimum sized compressor | $16,120 | $63,000 |
$15,101
235,955
kWh
|
$1,019
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $72,572 | $131,088 |
$46,573
727,728
kWh
|
$3,414
-
kW-mo/yr
|
$22,585
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $24,402 | $22,088 |
$22,625
353,532
kWh
|
$1,777
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs