Assessment Year | 2015 |
---|---|
Principal Product | Portuguese Bread |
NAICS | 311812: Commercial Bakeries |
SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
Sales Range | $1 M to 5M |
# of Employees | 140 |
Plant Area |
100,000
ft2
|
Annual Production | 10,000
lb
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $462,332 | 6,257,776 |
kWh
|
$0.074 |
Electricity Demand | $46,817 | 13,151 |
kW-mo/yr
|
$3.56 |
Electricity Fees | $217,002 | - |
|
- |
Natural Gas | $410,577 | 58,816 |
MMBtu
|
$6.98 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $113,824 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $65,897 | - |
$1,790
24,189
kWh
|
- |
$64,107
-
MMBtu
|
- | |
02 | 2.1224: Replace boiler | $16,261 | $75 | - | - |
$16,261
-
MMBtu
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,611 | $25 |
$3,387
45,777
kWh
|
$224
-
kW-mo/yr
|
- | - | |
04 | 2.2136: Install / repair insulation on steam lines | $914 | $200 | - | - |
$914
-
MMBtu
|
- | |
05 | 2.2443: Re-use or recycle hot or cold process exhaust air | $11,973 | $5,000 | - | - |
$11,973
-
MMBtu
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,528 | $5,688 |
$2,806
37,914
kWh
|
$121
-
kW-mo/yr
|
- | $601 | |
07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $734 | $1,500 | - | - |
$734
-
MMBtu
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,987 | $4,340 |
$1,862
25,160
kWh
|
$125
-
kW-mo/yr
|
- | - | |
09 | 2.2442: Preheat combustion air with waste heat | $8,298 | $20,000 | - | - |
$8,298
-
MMBtu
|
- | |
10 | 2.2136: Install / repair insulation on steam lines | $207 | $550 | - | - |
$207
-
MMBtu
|
- | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $415 | $1,615 |
$322
4,347
kWh
|
$71
-
kW-mo/yr
|
- | $22 | |
TOTAL RECOMMENDED | $113,824 | $38,993 |
$10,166
137,387
kWh
|
$541
-
kW-mo/yr
|
$102,494
-
MMBtu
|
$623 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs