Assessment Year 2013
Principal Product Fresh Veal and Lamb
NAICS 311612: Meat Processed from Carcasses
SIC 5147: Meats and Meat Products
Sales Range $100
M
to 500
M
# of Employees 50
Plant Area 100,000
ft2
Annual Production 19,500,000
lb
Production Hrs. Annual 6,240
hrs
Location (State) New Jersey

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $384,470 4,417,231
kWh
Electricity Demand $64,057 10,000
kW-mo/yr
Electricity Fees $133,921 -
Natural Gas $39,488 5,303
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $167,219 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Ancillary Material Cost Savings
01 2.3131: Reschedule plant operations or reduce load to avoid peaks $3,204 $3,144 - $3,204
-
kW-mo/yr
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $26,773 $22,500 $22,671
260,582
kWh
$2,679
-
kW-mo/yr
$1,423
03 2.7142: Utilize higher efficiency lamps and/or ballasts $2,705 $3,219 $2,418
27,795
kWh
$288
-
kW-mo/yr
$(-1.0)
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $111,477 $124,700 $101,234
1,163,614
kWh
$10,243
-
kW-mo/yr
-
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $22,891 $30,200 $20,789
238,959
kWh
$2,102
-
kW-mo/yr
-
06 2.7442: Keep doors and windows shut when not on use $169 $500 $169
1,940
kWh
- -
TOTAL RECOMMENDED $167,219 $184,263 $147,281
1,692,890
kWh
$18,516
-
kW-mo/yr
$1,422
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs