Assessment Year | 2012 |
---|---|
Principal Product | Woven Narrow Fabrics |
NAICS | 313220: Narrow Fabric Mills and Schiffli Machine Embroidery |
SIC | 2241: Narrow Fabric and Other Smallware Mills: Cotton, Wool, Silk, and Manmade Fiber |
Sales Range | $10 M to 50M |
# of Employees | 14 |
Plant Area |
104,730
ft2
|
Annual Production | 78,000,000
units
|
Production Hrs. Annual | 4,080
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $46,720 | 497,100 |
kWh
|
$0.094 |
Electricity Demand | $12,716 | 2,564 |
kW-mo/yr
|
$4.96 |
Electricity Fees | $3,948 | - |
|
- |
Natural Gas | $0.1 | 0 |
MMBtu
|
$5.00 |
Fuel Oil #4 | $284,966 | 13,161 |
MMBtu
|
$21.65 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $340,382 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $320,214 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Fuel Oil #4 Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $737 | $2,800 |
$639
6,795
kWh
|
$98
-
kW-mo/yr
|
- | - | - | |
02 | 2.2135: Repair and eliminate steam leaks | $16,178 | $750 | - | - | - | - |
$16,178
-
MMBtu
|
|
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,658 | $550 |
$1,435
15,262
kWh
|
$223
-
kW-mo/yr
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,195 | $6,750 |
$1,841
19,584
kWh
|
$286
-
kW-mo/yr
|
$68 | - | - | |
05 | 2.2136: Install / repair insulation on steam lines | $21,763 | $3,800 | - | - | - | - |
$21,763
-
MMBtu
|
|
06 | 2.7261: Install timers and/or thermostats | $6,352 | $575 |
$766
8,148
kWh
|
- | - | - |
$5,586
-
MMBtu
|
|
07 | 2.1224: Replace boiler | $226,873 | $560,000 | - | - | - |
$(-58,063.0)
-
MMBtu
|
$284,936
-
MMBtu
|
|
08 | 2.2444: Use hot process fluids to preheat incoming process fluids | $2,858 | $12,810 | - | - | - | - |
$2,858
-
MMBtu
|
|
09 | 2.2444: Use hot process fluids to preheat incoming process fluids | $3,306 | $3,800 | - | - | - | - |
$3,306
-
MMBtu
|
|
10 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,720 | $7,500 |
$4,120
43,829
kWh
|
$600
-
kW-mo/yr
|
- | - | - | |
11 | 2.2136: Install / repair insulation on steam lines | $53,742 | $3,200 | - | - | - | - |
$53,742
-
MMBtu
|
|
TOTAL RECOMMENDED | $340,382 | $602,535 |
$8,800
93,618
kWh
|
$1,207
-
kW-mo/yr
|
$68 |
$(-58,063.0)
-
MMBtu
|
$388,369
-
MMBtu
|
||
TOTAL IMPLEMENTED | $320,214 | $568,300 |
$1,435
15,262
kWh
|
$223
-
kW-mo/yr
|
- |
$(-58,063.0)
-
MMBtu
|
$376,619
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Fuel Oil #4 Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs