Assessment Year | 2009 |
---|---|
Principal Product | confections, snacks |
NAICS | 311352: Confectionery Manufacturing from Purchased Chocolate |
SIC | 2064: Candy and Other Confectionery Products |
Sales Range | $50 M to 100M |
# of Employees | 254 |
Plant Area |
200,000
ft2
|
Annual Production | 18,200,000
lb
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $326,152 | 7,333,200 |
kWh
|
$0.044 |
Electricity Demand | $158,198 | 25,957 |
kW-mo/yr
|
$6.09 |
Natural Gas | $228,749 | 24,919 |
MMBtu
|
$9.18 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $121,048 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,107 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4321: Upgrade obsolete equipment | $42,827 | $30,000 | - | - |
$42,827
-
MMBtu
|
|
02 | 2.2437: Recover waste heat from equipment | $26,473 | $20,000 | - | - |
$26,473
-
MMBtu
|
|
03 | 2.2437: Recover waste heat from equipment | $11,124 | $8,000 | - | - |
$11,124
-
MMBtu
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,628 | $1,760 |
$7,592
172,115
kWh
|
$2,036
-
kW-mo/yr
|
- | |
05 | 2.9112: Use solar heat to heat water | $7,038 | $28,000 | - | - |
$7,038
-
MMBtu
|
|
06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $6,526 | $8,000 | - | - |
$6,526
-
MMBtu
|
|
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,560 | $7,000 |
$3,585
81,518
kWh
|
$975
-
kW-mo/yr
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,911 | $320 |
$2,289
52,047
kWh
|
$622
-
kW-mo/yr
|
- | |
09 | 2.2113: Repair or replace steam traps | $2,855 | $2,000 | - | - |
$2,855
-
MMBtu
|
|
10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,713 | $224 |
$1,347
30,612
kWh
|
$366
-
kW-mo/yr
|
- | |
11 | 2.4221: Install compressor air intakes in coolest locations | $771 | $800 |
$594
13,487
kWh
|
$177
-
kW-mo/yr
|
- | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,937 | $10,491 |
$3,120
68,140
kWh
|
$817
-
kW-mo/yr
|
- | |
13 | 2.7135: Install occupancy sensors | $685 | $675 |
$685
15,581
kWh
|
- | - | |
TOTAL RECOMMENDED | $121,048 | $117,270 |
$19,212
433,500
kWh
|
$4,993
-
kW-mo/yr
|
$96,843
-
MMBtu
|
||
TOTAL IMPLEMENTED | $17,107 | $4,304 |
$11,228
254,774
kWh
|
$3,024
-
kW-mo/yr
|
$2,855
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs