Assessment Year | 2008 |
---|---|
Principal Product | Batteries |
NAICS | 335911: Storage Battery Manufacturing |
SIC | 3691: Storage Batteries |
Sales Range | $10 M to 50M |
# of Employees | 280 |
Plant Area |
105,000
ft2
|
Annual Production | 2,000,000
units
|
Production Hrs. Annual | 5,880
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $781,167 | 17,028,555 |
kWh
|
$0.046 |
Electricity Demand | $322,464 | 33,869 |
kW-mo/yr
|
$9.52 |
Natural Gas | $747,242 | 78,692 |
MMBtu
|
$9.50 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $630,281 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,862 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.1321: Replace fossil fuel equipment with electrical equipment | $331,483 | $16,000 | - | - |
$331,483
-
MMBtu
|
|
02 | 2.9114: Use solar heat to make electricty | $104,249 | $671,675 |
$104,249
1,551,330
kWh
|
- | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $71,498 | $60,000 |
$54,924
1,194,005
kWh
|
$16,574
-
kW-mo/yr
|
- | |
04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $25,491 | $15,000 | - | - |
$25,491
-
MMBtu
|
|
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $16,931 | - |
$13,009
282,809
kWh
|
$3,922
-
kW-mo/yr
|
- | |
06 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $42,587 | $65,000 | - |
$42,587
-
kW-mo/yr
|
- | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,832 | $2,200 |
$4,042
87,858
kWh
|
$790
-
kW-mo/yr
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,134 | $700 |
$1,534
33,357
kWh
|
$600
-
kW-mo/yr
|
- | |
09 | 2.6218: Turn off equipment when not in use | $931 | - | - | - |
$931
-
MMBtu
|
|
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $28,056 | $46,378 |
$18,966
412,294
kWh
|
$9,090
-
kW-mo/yr
|
- | |
11 | 2.7135: Install occupancy sensors | $2,089 | $780 |
$2,089
45,422
kWh
|
- | - | |
TOTAL RECOMMENDED | $630,281 | $877,733 |
$198,813
3,607,075
kWh
|
$73,563
-
kW-mo/yr
|
$357,905
-
MMBtu
|
||
TOTAL IMPLEMENTED | $17,862 | - |
$13,009
282,809
kWh
|
$3,922
-
kW-mo/yr
|
$931
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs