Assessment Year | 2007 |
---|---|
Principal Product | Thermoplastic Compounds |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 3087: Custom Compounding of Purchased Plastics Resins |
Sales Range | $10 M to 50M |
# of Employees | 86 |
Plant Area |
194,447
ft2
|
Annual Production | 1,700
ton
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $560,464 | 7,112,361 |
kWh
|
$0.079 |
Electricity Demand | $106,612 | 16,529 |
kW-mo/yr
|
$6.45 |
Natural Gas | $113,894 | 6,989 |
MMBtu
|
$16.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $65,678 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $48,543 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4322: Use or replace with energy efficient substitutes | $25,680 | $50,000 | - | - | - | $25,680 | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,103 | $2,500 |
$9,046
114,525
kWh
|
$1,057
-
kW-mo/yr
|
- | - | |
03 | 2.7261: Install timers and/or thermostats | $4,204 | $2,000 | - | - |
$4,204
-
MMBtu
|
- | |
04 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $4,727 | $2,250 |
$4,233
53,587
kWh
|
$494
-
kW-mo/yr
|
- | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,084 | $500 |
$3,564
45,118
kWh
|
$520
-
kW-mo/yr
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,514 | $200 |
$3,147
39,831
kWh
|
$367
-
kW-mo/yr
|
- | - | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,184 | $2,500 |
$2,852
36,097
kWh
|
$332
-
kW-mo/yr
|
- | - | |
08 | 2.4314: Use synthetic lubricant | $3,151 | $500 |
$2,822
35,718
kWh
|
$329
-
kW-mo/yr
|
- | - | |
09 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $2,674 | $5,000 | - | - |
$2,674
-
MMBtu
|
- | |
10 | 2.4221: Install compressor air intakes in coolest locations | $1,288 | $1,000 |
$1,166
14,758
kWh
|
$122
-
kW-mo/yr
|
- | - | |
11 | 2.7135: Install occupancy sensors | $3,069 | $750 |
$3,069
29,447
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $65,678 | $67,200 |
$29,899
369,081
kWh
|
$3,221
-
kW-mo/yr
|
$6,878
-
MMBtu
|
$25,680 | ||
TOTAL IMPLEMENTED | $48,543 | $58,500 |
$16,628
210,498
kWh
|
$2,031
-
kW-mo/yr
|
$4,204
-
MMBtu
|
$25,680 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs