Assessment Year | 2005 |
---|---|
Principal Product | Engraving and printing stationary supplies |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 280 |
Plant Area |
154,000
ft2
|
Annual Production | 151,000,000
pieces
|
Production Hrs. Annual | 3,120
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $140,746 | 1,674,800 |
kWh
|
$0.084 |
Electricity Demand | $56,497 | 6,586 |
kW-mo/yr
|
$8.58 |
Natural Gas | $42,751 | 3,000 |
MMBtu
|
$14.25 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $464,504 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $14,289 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $444,462 | $1,100,000 |
$39,230
467,030
kWh
|
$15,276
-
kW-mo/yr
|
- | $389,956 | |
02 | 2.1224: Replace boiler | $5,753 | $74,500 | - | - |
$5,753
-
MMBtu
|
- | |
03 | 2.7221: Lower temperature during the winter season and vice-versa | $4,650 | $50 |
$3,339
39,746
kWh
|
$1,311
-
kW-mo/yr
|
- | - | |
04 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $2,831 | $2,500 | - |
$2,831
-
kW-mo/yr
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,281 | $100 |
$1,637
19,494
kWh
|
$644
-
kW-mo/yr
|
- | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,391 | $250 |
$979
11,653
kWh
|
$412
-
kW-mo/yr
|
- | - | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $844 | $80 |
$483
5,746
kWh
|
$361
-
kW-mo/yr
|
- | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $457 | $1,000 |
$261
3,109
kWh
|
$196
-
kW-mo/yr
|
- | - | |
09 | 2.7135: Install occupancy sensors | $375 | $300 |
$375
4,465
kWh
|
- | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,460 | - |
$1,048
12,840
kWh
|
$412
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $464,504 | $1,178,780 |
$47,352
564,083
kWh
|
$21,443
-
kW-mo/yr
|
$5,753
-
MMBtu
|
$389,956 | ||
TOTAL IMPLEMENTED | $14,289 | $4,280 |
$8,122
97,053
kWh
|
$6,167
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs