Assessment Year | 2003 |
---|---|
Principal Product | Silicone Rubber / PTFE Laminates |
NAICS | 315990: Apparel Accessories and Other Apparel Manufacturing |
SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
135,000
ft2
|
Annual Production | 25,000,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Delaware |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $274,137 | 8,233,665 |
kWh
|
$0.033 |
Electricity Demand | $255,683 | 24,368 |
kW-mo/yr
|
$10.49 |
Natural Gas | $255,683 | 37,876 |
MMBtu
|
$6.75 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $61,432 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7447: Install vinyl strip / high speed / air curtain doors | $15,185 | $6,000 | - | - | - |
$15,185
-
MMBtu
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,795 | $75,903 |
$5,577
169,004
kWh
|
$2,730
-
kW-mo/yr
|
- | - | - | $4,488 | |
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $7,543 | $750 | - | - | - |
$7,543
-
MMBtu
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,515 | $300 |
$4,042
122,485
kWh
|
$2,473
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.2511: Insulate bare equipment | $5,757 | $720 |
$5,757
174,455
kWh
|
- | - | - | - | - | |
06 | 3.5316: Contract a wood pallet recycling company | $4,940 | - | - | - | - | - |
$4,940
-
lb
|
- | |
07 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $3,837 | $2,500 | - |
$3,837
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.3212: Optimize plant power factor | $1,521 | $6,250 | - | - | $1,521 | - | - | - | |
09 | 2.3132: Recharge batteries on during off-peak demand periods | $1,371 | - | - |
$1,371
-
kW-mo/yr
|
- | - | - | - | |
10 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $761 | - |
$430
13,021
kWh
|
$331
-
kW-mo/yr
|
- | - | - | - | |
11 | 2.4231: Reduce the pressure of compressed air to the minimum required | $702 | - |
$702
21,285
kWh
|
- | - | - | - | - | |
12 | 2.7124: Make a practice of turning off lights when not needed | $505 | - |
$505
15,306
kWh
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $61,432 | $92,423 |
$17,013
515,556
kWh
|
$10,742
-
kW-mo/yr
|
$1,521 |
$22,728
-
MMBtu
|
$4,940
-
lb
|
$4,488 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs