Assessment Year | 2003 |
---|---|
Principal Product | PVC and CPVC Pipe |
NAICS | 326122: Plastics Pipe and Pipe Fitting Manufacturing |
SIC | 3084: Plastics Pipe |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
250,000
ft2
|
Annual Production | 34,000,000
lb
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $176,660 | 6,239,510 |
kWh
|
$0.028 |
Electricity Demand | $258,301 | 15,750 |
kW-mo/yr
|
$16.40 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $36,132 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,043 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $1,097 | $1,000 |
$495
17,486
kWh
|
$602
-
kW-mo/yr
|
|
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $578 | - |
$578
20,428
kWh
|
- | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,005 | - |
$2,098
74,123
kWh
|
$1,907
-
kW-mo/yr
|
|
04 | 2.4314: Use synthetic lubricant | $17,409 | $1,000 |
$2,141
75,643
kWh
|
$15,268
-
kW-mo/yr
|
|
05 | 2.2515: Use optimum thickness insulation | $13,043 | $2,731 |
$7,564
267,298
kWh
|
$5,479
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $36,132 | $4,731 |
$12,876
454,978
kWh
|
$23,256
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $13,043 | $2,731 |
$7,564
267,298
kWh
|
$5,479
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs