Assessment Year | 2003 |
---|---|
Principal Product | Plactic Bags and Films |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $5 M to 10M |
# of Employees | 40 |
Plant Area |
47,000
ft2
|
Annual Production | 7,200,000
lb
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $221,999 | 2,318,613 |
kWh
|
$0.096 |
Electricity Demand | $54,882 | 6,045 |
kW-mo/yr
|
$9.08 |
Natural Gas | $31,900 | 3,650 |
MMBtu
|
$8.74 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $24,575 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,050 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $947 | - |
$716
10,279
kWh
|
$231
-
kW-mo/yr
|
- | - | |
02 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $3,269 | $2,500 | - |
$3,269
-
kW-mo/yr
|
- | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $7,520 | - |
$6,014
86,288
kWh
|
$1,506
-
kW-mo/yr
|
- | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,873 | - |
$3,873
55,564
kWh
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,288 | $300 |
$1,823
26,161
kWh
|
$465
-
kW-mo/yr
|
- | - | |
06 | 2.2511: Insulate bare equipment | $588 | $925 |
$470
6,736
kWh
|
$118
-
kW-mo/yr
|
- | - | |
07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $795 | $500 | - | - | - |
$795
-
MMBtu
|
|
08 | 2.8123: Pay utility bills on time | $4,771 | - | - | - | $4,771 | - | |
09 | 2.7124: Make a practice of turning off lights when not needed | $273 | - |
$273
3,917
kWh
|
- | - | - | |
10 | 2.4314: Use synthetic lubricant | $251 | $200 |
$205
2,934
kWh
|
$46
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $24,575 | $4,425 |
$13,374
191,879
kWh
|
$5,635
-
kW-mo/yr
|
$4,771 |
$795
-
MMBtu
|
||
TOTAL IMPLEMENTED | $16,050 | $500 |
$9,031
129,579
kWh
|
$2,248
-
kW-mo/yr
|
$4,771 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs