| Assessment Year | 2002 |
|---|---|
| Principal Product | Printing Material |
| NAICS |
n/a
|
| SIC | 2761: Manifold Business Forms |
| Sales Range | $5 M to 10M |
| # of Employees | 65 |
| Plant Area |
44,000
ft2
|
| Annual Production | 8,000,000
lb
|
| Production Hrs. Annual | 4,160
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $149,037 | 1,258,165 |
kWh
|
$0.12 |
| Electricity Demand | $31,667 | 3,958 |
kW-mo/yr
|
$8.00 |
| Natural Gas | $6,427 | 629 |
MMBtu
|
$10.22 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $23,471 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,218 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,365 | - |
$2,749
29,564
kWh
|
$616
-
kW-mo/yr
|
- | - | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $929 | $1,000 |
$619
6,654
kWh
|
$310
-
kW-mo/yr
|
- | - | |
| 03 | 2.4323: Use optimum size and capacity equipment | $3,820 | - |
$3,820
32,254
kWh
|
- | - | - | |
| 04 | 2.2437: Recover waste heat from equipment | $3,018 | $920 |
$416
4,474
kWh
|
- |
$2,602
-
MMBtu
|
- | |
| 05 | 3.5316: Contract a wood pallet recycling company | $4,000 | - | - | - | - |
$4,000
-
lb
|
|
| 06 | 2.2426: Use waste heat from flue gases to heat space conditioning air | $7,306 | $10,000 | - | - |
$7,306
-
MMBtu
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,033 | $3,718 |
$862
9,266
kWh
|
$171
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $23,471 | $15,638 |
$8,466
82,212
kWh
|
$1,097
-
kW-mo/yr
|
$9,908
-
MMBtu
|
$4,000
-
lb
|
||
| TOTAL IMPLEMENTED | $8,218 | $3,718 |
$7,431
71,084
kWh
|
$787
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs