Assessment Year | 2001 |
---|---|
Principal Product | Bottling |
NAICS |
n/a
|
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $10 M to 50M |
# of Employees | 160 |
Plant Area |
119,985
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 2,040
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $192,825 | 2,643,600 |
kWh
|
$0.073 |
Electricity Demand | $54,714 | 7,884 |
kW-mo/yr
|
$6.94 |
Natural Gas | $152,367 | 20,774 |
MMBtu
|
$7.33 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $43,190 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,336 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $979 | $1,000 |
$493
9,440
kWh
|
$486
-
kW-mo/yr
|
- | - | |
02 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $29,762 | $76,790 | - | - |
$29,762
-
MMBtu
|
- | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,037 | - |
$1,026
19,655
kWh
|
$1,011
-
kW-mo/yr
|
- | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,376 | - |
$1,376
26,366
kWh
|
- | - | - | |
05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $76 | $300 | - | - |
$76
-
MMBtu
|
- | |
06 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $8,207 | $2,500 | - |
$8,207
-
kW-mo/yr
|
- | - | |
07 | 3.4113: Treat and reuse rinse waters | $753 | $3,750 | - | - | - |
$753
-
Tgal
|
|
TOTAL RECOMMENDED | $43,190 | $84,340 |
$2,895
55,461
kWh
|
$9,704
-
kW-mo/yr
|
$29,838
-
MMBtu
|
$753
-
Tgal
|
||
TOTAL IMPLEMENTED | $10,336 | $6,250 |
$1,376
26,366
kWh
|
$8,207
-
kW-mo/yr
|
- |
$753
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs