| Assessment Year | 2000 |
|---|---|
| Principal Product | ergonomic chairs |
| NAICS |
n/a
|
| SIC | 2522: Office Furniture, Except Wood |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
150,000
ft2
|
| Annual Production | 100,800
pieces
|
| Production Hrs. Annual | 2,125
hrs
|
| Location (State) | Kansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $42,182 | 955,158 |
kWh
|
$0.044 |
| Electricity Demand | $19,430 | 3,604 |
kW-mo/yr
|
$5.39 |
| Natural Gas | $58,361 | 15,755 |
MMBtu
|
$3.70 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $22,180 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $3,740 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4226: Use / purchase optimum sized compressor | $5,290 | $900 |
$2,980
72,098
kWh
|
$2,310
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 2.7124: Make a practice of turning off lights when not needed | $2,380 | $600 |
$1,980
48,066
kWh
|
$130
-
kW-mo/yr
|
- | - | - | $270 | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,010 | $330 |
$1,130
27,257
kWh
|
$880
-
kW-mo/yr
|
- | - | - | - | |
| 04 | 2.1113: Reduce combustion air flow to optimum | $1,730 | - | - | - | - |
$1,730
-
MMBtu
|
- | - | |
| 05 | 2.3212: Optimize plant power factor | $980 | $1,650 | - | - | $980 | - | - | - | |
| 06 | 2.2437: Recover waste heat from equipment | $900 | $2,400 | - | - | - |
$900
-
MMBtu
|
- | - | |
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $650 | $830 |
$370
8,792
kWh
|
$280
-
kW-mo/yr
|
- | - | - | - | |
| 08 | 3.4111: Use closed cycle process to minimize waste water production | $6,680 | $2,150 |
$(-120.0)
(-2,638)
kWh
|
$(-80.0)
-
kW-mo/yr
|
- | - |
$6,880
-
Tgal
|
- | |
| 09 | 3.4151: Minimize water usage | $1,560 | $2,025 | - | - | - | - |
$1,560
-
Tgal
|
- | |
| TOTAL RECOMMENDED | $22,180 | $10,885 |
$6,340
153,575
kWh
|
$3,520
-
kW-mo/yr
|
$980 |
$2,630
-
MMBtu
|
$8,440
-
Tgal
|
$270 | ||
| TOTAL IMPLEMENTED | $3,740 | $330 |
$1,130
27,257
kWh
|
$880
-
kW-mo/yr
|
- |
$1,730
-
MMBtu
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs