| Assessment Year | 2000 |
|---|---|
| Principal Product | comercial turf equipment |
| NAICS |
n/a
|
| SIC | 3523: Farm Machinery and Equipment |
| Sales Range | $10 M to 50M |
| # of Employees | 160 |
| Plant Area |
95,707
ft2
|
| Annual Production | 2,320
pieces
|
| Production Hrs. Annual | 6,120
hrs
|
| Location (State) | Kansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $85,846 | 2,319,461 |
kWh
|
$0.037 |
| Electricity Demand | $88,265 | 7,740 |
kW-mo/yr
|
$11.40 |
| Natural Gas | $48,149 | 12,600 |
MMBtu
|
$3.82 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $71,230 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4226: Use / purchase optimum sized compressor | $3,370 | $10,180 |
$3,370
94,373
kWh
|
- | - | - | - | - | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,240 | $450 |
$1,390
38,687
kWh
|
$850
-
kW-mo/yr
|
- | - | - | - | - | |
| 03 | 2.3212: Optimize plant power factor | $2,000 | $2,400 | - |
$2,000
-
kW-mo/yr
|
- | - | - | - | - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $680 | $70 |
$420
11,723
kWh
|
$260
-
kW-mo/yr
|
- | - | - | - | - | |
| 05 | 3.4111: Use closed cycle process to minimize waste water production | $20,800 | $9,400 |
$(-790.0)
(-21,981)
kWh
|
$(-490.0)
-
kW-mo/yr
|
$22,080
-
Tgal
|
- | - | - | - | |
| 06 | 3.8142: Distill contaminated solvents for reuse | $5,920 | $240 | - |
$(-570.0)
-
kW-mo/yr
|
- |
$2,060
-
gal
|
$(-3,630.0) | - | $8,060 | |
| 07 | 4.446: Automate finishing process | $33,420 | $92,600 |
$(-1,160.0)
(-32,532)
kWh
|
$(-2,020.0)
-
kW-mo/yr
|
- | - | $36,600 | - | - | |
| 08 | 4.611: Begin a practice of predictive / preventative maintenance | $2,800 | $6,000 | - | - | - | - | - | $2,800 | - | |
| TOTAL RECOMMENDED | $71,230 | $121,340 |
$3,230
90,270
kWh
|
$30
-
kW-mo/yr
|
$22,080
-
Tgal
|
$2,060
-
gal
|
$32,970 | $2,800 | $8,060 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs