Assessment Year 1994
Principal Product containers
NAICS
n/a
SIC 3085: Plastics Bottles
Sales Range $10
M
to 50
M
# of Employees 230
Plant Area 52,000
ft2
Annual Production 400,000
pieces
Production Hrs. Annual 8,568
hrs
Location (State) Missouri

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $362,780 6,282,532
kWh
Natural Gas $21,635 4,241
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $40,819 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $37,943

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings
01 2.4133: Use most efficient type of electric motors $18,883 $17,955 $18,883
327,081
kWh
02 2.4111: Utilize energy-efficient belts and other improved mechanisms $7,885 $669 $7,885
136,577
kWh
03 2.4133: Use most efficient type of electric motors $4,027 $2,519 $4,027
69,754
kWh
04 2.7142: Utilize higher efficiency lamps and/or ballasts $4,251 $5,809 $4,251
57,444
kWh
05 2.7135: Install occupancy sensors $1,794 $1,350 $1,794
31,067
kWh
06 2.7134: Use photocell controls $305 $60 $305
5,275
kWh
07 2.7142: Utilize higher efficiency lamps and/or ballasts $458 $540 $458
4,689
kWh
08 2.7142: Utilize higher efficiency lamps and/or ballasts $340 $220 $340
2,345
kWh
09 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,489 $3,000 $1,489
25,791
kWh
10 2.4221: Install compressor air intakes in coolest locations $1,387 $90 $1,387
24,033
kWh
TOTAL RECOMMENDED $40,819 $32,212 $40,819
684,056
kWh
TOTAL IMPLEMENTED $37,943 $29,122 $37,943
634,232
kWh
Yearly Savings* Imp'd Cost* Electricity Usage Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs