Assessment Year | 1989 |
---|---|
Principal Product | INJECTION MOLDED PRODUCT |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
n/a
|
Annual Production | 10,000,000
lb
|
Production Hrs. Annual | 6,720
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $407,361 | 7,031,946 |
kWh
|
$0.058 |
Natural Gas | $32,465 | 9,396 |
MMBtu
|
$3.46 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $31,424 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $31,424 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,513 | $6,446 |
$3,513
60,668
kWh
|
- | |
02 | 2.6121: Reduce hot water temperature to the minimum required | $235 | - |
$204
3,517
kWh
|
$31
-
MMBtu
|
|
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,139 | $500 |
$3,139
54,220
kWh
|
- | |
04 | 2.1123: Install automatic stack damper | $6,820 | $5,625 | - |
$6,820
-
MMBtu
|
|
05 | 2.4133: Use most efficient type of electric motors | $2,698 | $1,800 |
$2,698
46,600
kWh
|
- | |
06 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $14,815 | $20,000 |
$14,815
255,862
kWh
|
- | |
07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $204 | $250 | - |
$204
-
MMBtu
|
|
TOTAL RECOMMENDED | $31,424 | $34,621 |
$24,369
420,867
kWh
|
$7,055
-
MMBtu
|
||
TOTAL IMPLEMENTED | $31,424 | $34,621 |
$24,369
420,867
kWh
|
$7,055
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs