| Assessment Year | 1989 |
|---|---|
| Principal Product | FURFURAL AND ALCOHOL |
| NAICS |
n/a
|
| SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 107 |
| Plant Area |
n/a
|
| Annual Production | 40,000,000
lb
|
| Production Hrs. Annual | 7,848
hrs
|
| Location (State) | Nebraska |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $654,739 | 18,756,448 |
kWh
|
$0.035 |
| Natural Gas | $177,602 | 63,884 |
MMBtu
|
$2.78 |
| LPG | $880 | 275 |
MMBtu
|
$3.20 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $995,258 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $995,258 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | LPG Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3412: Use waste heat to produce steam to drive a steam turbine-generator | $831,745 | $1,230,000 |
$654,884
18,762,017
kWh
|
- | - | $176,861 | |
| 02 | 2.2692: Use outside cold water source as a supply of cooling water | $139,391 | $226,000 |
$2,670
76,495
kWh
|
- | - | $136,721 | |
| 03 | 2.6232: Install set-back timers | $16,143 | $5,856 |
$16,143
462,485
kWh
|
- | - | - | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,092 | $3,080 |
$4,092
117,233
kWh
|
- | - | - | |
| 05 | 2.4312: Improve lubrication practices | $2,169 | - |
$2,169
62,134
kWh
|
- | - | - | |
| 06 | 2.7291: Reschedule and rearrange multiple-source heating systems | $618 | - | - | - |
$618
-
MMBtu
|
- | |
| 07 | 2.4133: Use most efficient type of electric motors | $931 | $1,018 |
$931
26,671
kWh
|
- | - | - | |
| 08 | 2.6121: Reduce hot water temperature to the minimum required | $169 | - | - |
$169
-
MMBtu
|
- | - | |
| TOTAL RECOMMENDED | $995,258 | $1,465,954 |
$680,889
19,507,035
kWh
|
$169
-
MMBtu
|
$618
-
MMBtu
|
$313,582 | ||
| TOTAL IMPLEMENTED | $995,258 | $1,465,954 |
$680,889
19,507,035
kWh
|
$169
-
MMBtu
|
$618
-
MMBtu
|
$313,582 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | LPG Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs