Assessment Year | 2007 |
---|---|
Principal Product | Newspapers |
NAICS | 511110: Newspaper Publishers |
SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
Sales Range | $50 M to 100M |
# of Employees | 450 |
Plant Area |
350,000
ft2
|
Annual Production | 70,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,287,669 | 18,740,398 |
kWh
|
$0.069 |
Electricity Demand | $400,042 | 40,245 |
kW-mo/yr
|
$9.94 |
Electricity Fees | $147,201 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $226,415 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $70,318 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|
01 | 2.2628: Utilize a less expensive cooling method | $127,674 | $105,070 |
$105,825
1,511,782
kWh
|
$21,849
-
kW-mo/yr
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $37,375 | $30 |
$30,572
436,736
kWh
|
$6,803
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $18,482 | $1,074 |
$18,182
265,042
kWh
|
$300
-
kW-mo/yr
|
- | |
04 | 2.2447: Heat water with exhaust heat | $14,461 | $1,349 |
$11,908
176,082
kWh
|
$2,553
-
kW-mo/yr
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,799 | $14,700 |
$11,436
163,374
kWh
|
$2,363
-
kW-mo/yr
|
- | |
06 | 2.7134: Use photocell controls | $6,838 | $770 |
$5,211
77,482
kWh
|
$1,627
-
kW-mo/yr
|
- | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $5,866 | $2,373 |
$5,762
82,741
kWh
|
$104
-
kW-mo/yr
|
- | |
08 | 3.4116: Meter recycled water (to reduce sewer charges) | $1,920 | $4,160 | - | - |
$1,920
-
Tgal
|
|
TOTAL RECOMMENDED | $226,415 | $129,526 |
$188,896
2,713,239
kWh
|
$35,599
-
kW-mo/yr
|
$1,920
-
Tgal
|
||
TOTAL IMPLEMENTED | $70,318 | $2,453 |
$60,662
877,860
kWh
|
$9,656
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs