Assessment Year 1986
Principal Product CORRUG SHIPPING CONTAINE
NAICS
n/a
SIC 2653: Corrugated and Solid Fiber Boxes
Sales Range $10
M
to 50
M
# of Employees 149
Plant Area
n/a
Annual Production 595,000
thousand feet
Production Hrs. Annual 5,880
hrs
Location (State) Missouri

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $287,215 5,590,856
kWh
Natural Gas $145,801 41,629
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $23,436 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $9,881

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.6232: Install set-back timers $5,120 $680 $5,120
99,648
kWh
-
02 2.4312: Improve lubrication practices $5,482 $2,700 $5,482
106,682
kWh
-
03 2.2414: Use waste heat from hot flue gases to preheat $4,029 $4,000 - $4,029
-
MMBtu
05 2.2121: Increase amount of condensate returned $1,050 $1,500 - $1,050
-
MMBtu
06 2.1123: Install automatic stack damper $2,153 $600 - $2,153
-
MMBtu
08 2.1233: Analyze flue gas for proper air/fuel ratio $1,183 $2,500 - $1,183
-
MMBtu
09 2.2511: Insulate bare equipment $1,183 $1,000 - $1,183
-
MMBtu
10 2.4231: Reduce the pressure of compressed air to the minimum required $708 $30 $708
13,775
kWh
-
11 2.6121: Reduce hot water temperature to the minimum required $375 - - $375
-
MMBtu
12 2.1131: Repair faulty insulation in furnaces, boilers, etc $210 $245 - $210
-
MMBtu
13 2.7142: Utilize higher efficiency lamps and/or ballasts $1,943 $1,940 $1,943
37,808
kWh
-
TOTAL RECOMMENDED $23,436 $15,195 $13,253
257,913
kWh
$10,183
-
MMBtu
TOTAL IMPLEMENTED $9,881 $6,865 $7,063
137,456
kWh
$2,818
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs