| Assessment Year | 1986 |
|---|---|
| Principal Product | PRINTED PAPER |
| NAICS |
n/a
|
| SIC | 2752: Commercial Printing, Lithographic |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
n/a
|
| Annual Production | 11,000
ton
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $354,631 | 6,458,968 |
kWh
|
$0.055 |
| Natural Gas | $108,700 | 26,456 |
MMBtu
|
$4.11 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $137,726 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $25,489 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $109,167 | $1,000,000 |
$331,148
6,031,946
kWh
|
$(-221,981.0)
-
MMBtu
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,883 | $10,000 |
$14,883
271,102
kWh
|
- | - | |
| 03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,269 | $20 |
$2,269
41,325
kWh
|
- | - | |
| 04 | 2.4221: Install compressor air intakes in coolest locations | $418 | $700 |
$418
7,620
kWh
|
- | - | |
| 05 | 2.1123: Install automatic stack damper | $3,144 | $3,000 | - |
$3,144
-
MMBtu
|
- | |
| 06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $882 | $2,000 | - |
$1,032
-
MMBtu
|
$(-150.0) | |
| 07 | 2.2422: Use waste heat from hot flue gases to generate steam | $801 | $1,400 | - |
$801
-
MMBtu
|
- | |
| 08 | 2.6121: Reduce hot water temperature to the minimum required | $160 | - | - |
$160
-
MMBtu
|
- | |
| 09 | 2.4312: Improve lubrication practices | $6,002 | $4,500 |
$6,002
109,320
kWh
|
- | - | |
| TOTAL RECOMMENDED | $137,726 | $1,021,620 |
$354,720
6,461,313
kWh
|
$(-216,844.0)
-
MMBtu
|
$(-150.0) | ||
| TOTAL IMPLEMENTED | $25,489 | $20,200 |
$21,303
388,042
kWh
|
$4,336
-
MMBtu
|
$(-150.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs