Assessment Year | 2017 |
---|---|
Principal Product | Personal care and incontinence products |
NAICS | 322291: Sanitary Paper Product Manufacturing |
SIC | 2676: Sanitary Paper Products |
Sales Range | $50 M to 100M |
# of Employees | 150 |
Plant Area |
675,000
ft2
|
Annual Production | 542,000,000
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,175,679 | 25,725,213 |
kWh
|
$0.046 |
Electricity Demand | $730,267 | 60,092 |
kW-mo/yr
|
$12.15 |
Electricity Fees | $(-140,484.0) | - |
|
- |
Natural Gas | $76,153 | 13,090 |
MMBtu
|
$5.82 |
TOTAL YEARLY COSTS | $1,841,615 | |||
RECOMMENDED SAVINGS* | $156,033 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $115,407 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $35,480 | $18,700 |
$35,480
771,298
kWh
|
- | - | - | |
02 | 2.3212: Optimize plant power factor | $15,401 | $43,120 | - | - | $15,401 | - | |
03 | 2.7224: Reduce space conditioning during non-working hours | $20,970 | - |
$8,236
179,040
kWh
|
- | - |
$12,734
-
MMBtu
|
|
04 | 2.4238: Do not use compressed air for personal cooling | $36,644 | $16,350 | - | - | - |
$36,644
-
MMBtu
|
|
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $12,541 | - |
$8,009
174,112
kWh
|
$4,532
-
kW-mo/yr
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,756 | $5,320 |
$13,756
299,040
kWh
|
- | - | - | |
07 | 2.4235: Remove or close off unneeded compressed air lines | $9,390 | $9,300 |
$9,390
204,120
kWh
|
- | - | - | |
08 | 2.7135: Install occupancy sensors | $5,402 | $8,550 |
$5,402
117,437
kWh
|
- | - | - | |
09 | 2.7134: Use photocell controls | $1,262 | $630 |
$1,262
27,429
kWh
|
- | - | - | |
10 | 2.2615: Clean condenser tubes | $2,467 | $650 |
$2,467
53,634
kWh
|
- | - | - | |
11 | 2.5123: Reduce fluid flow rates | $2,428 | $1,125 |
$1,408
30,605
kWh
|
$1,020
-
kW-mo/yr
|
- | - | |
12 | 2.4323: Use optimum size and capacity equipment | $292 | $775 |
$292
6,340
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $156,033 | $104,520 |
$85,702
1,863,055
kWh
|
$5,552
-
kW-mo/yr
|
$15,401 |
$49,378
-
MMBtu
|
||
TOTAL IMPLEMENTED | $115,407 | $85,640 |
$82,740
1,798,681
kWh
|
$4,532
-
kW-mo/yr
|
$15,401 |
$12,734
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs