| Assessment Year | 1983 |
|---|---|
| Principal Product | CONCRETE REINFORCED PIPE |
| NAICS |
n/a
|
| SIC | 3272: Concrete Products, Except Block and Brick |
| Sales Range | $10 M to 50M |
| # of Employees | 130 |
| Plant Area |
n/a
|
| Annual Production | 7,000
thousand feet
|
| Production Hrs. Annual | 2,365
hrs
|
| Location (State) | Kansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $147,998 | 1,663,247 |
kWh
|
$0.089 |
| Natural Gas | $269,198 | 79,808 |
MMBtu
|
$3.37 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $115,739 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $109,016 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2424: Use heat in flue gases to preheat products or materials | $51,514 | $55,000 | - |
$51,514
-
MMBtu
|
|
| 02 | 2.2191: Substitute hot process fluids for steam | $30,320 | - | - |
$30,320
-
MMBtu
|
|
| 03 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $2,372 | $10,000 | - |
$2,372
-
MMBtu
|
|
| 04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $8,586 | $1,400 | - |
$8,586
-
MMBtu
|
|
| 05 | 2.1123: Install automatic stack damper | $4,345 | $912 | - |
$4,345
-
MMBtu
|
|
| 06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $3,751 | $2,228 | - |
$3,751
-
MMBtu
|
|
| 07 | 2.1135: Repair furnaces and oven doors so that they seal efficiently | $2,986 | $1,142 | - |
$2,986
-
MMBtu
|
|
| 08 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,716 | $550 | - |
$2,716
-
MMBtu
|
|
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,426 | $6,017 |
$2,426
27,257
kWh
|
- | |
| 10 | 2.1242: Minimize boiler blowdown with better feedwater treatment | $2,147 | $4,000 | - |
$2,147
-
MMBtu
|
|
| 11 | 2.7221: Lower temperature during the winter season and vice-versa | $2,094 | - |
$2,094
23,447
kWh
|
- | |
| 12 | 2.3212: Optimize plant power factor | $1,735 | $970 |
$1,735
-
kWh
|
- | |
| 13 | 2.3212: Optimize plant power factor | $747 | $540 |
$747
-
kWh
|
- | |
| TOTAL RECOMMENDED | $115,739 | $82,759 |
$7,002
50,704
kWh
|
$108,737
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $109,016 | $77,249 |
$2,426
27,257
kWh
|
$106,590
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs