| Assessment Year | 2022 |
|---|---|
| Principal Product | Aluminum Knuckles |
| NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | $10 M to 50M |
| # of Employees | 393 |
| Plant Area |
130,000
ft2
|
| Annual Production | 2,100,000
units
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $1,036,757 | 20,618,215 |
kWh
|
$0.050 | |
| Electricity Demand | $247,611 | 47,236 |
kW-mo/yr
|
$5.24 | |
| Electricity Fees | $38,424 | - |
|
- | |
| Natural Gas | $240,911 | 53,154 |
MMBtu
|
$4.53 | |
| Waste Disposal Costs | |||||
| Water Usage | $12,693 | 3,154 |
Tgal
|
$4.02 | |
| Water Disposal | $27,960 | 3,154 |
Tgal
|
$8.86 | |
| TOTAL YEARLY COSTS | $1,604,356 | ||||
| RECOMMENDED SAVINGS* | $638,178 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $38,106 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.8121: Apply for tax-free status for energy purchases | $28,812 | $1,600 | - | - | $11,153 | $17,659 | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,721 | $18,007 |
$3,460
68,787
kWh
|
$747
-
kW-mo/yr
|
$514 | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,500 | $5,480 |
$6,249
124,243
kWh
|
$1,251
-
kW-mo/yr
|
- | - | |
| 04 | 2.6127: Maintain air filters by cleaning or replacement | $2,371 | $2,138 |
$1,975
39,260
kWh
|
$396
-
kW-mo/yr
|
- | - | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,662 | $2,460 |
$2,217
44,070
kWh
|
$445
-
kW-mo/yr
|
- | - | |
| 06 | 2.7442: Keep doors and windows shut when not on use | $2,202 | - |
$1,835
36,480
kWh
|
$367
-
kW-mo/yr
|
- | - | |
| 07 | 2.9114: Use solar heat to make electricty | $589,910 | $5,416,800 |
$547,262
10,879,955
kWh
|
$42,648
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $638,178 | $5,446,485 |
$562,998
11,192,795
kWh
|
$45,854
-
kW-mo/yr
|
$11,667 | $17,659 | ||
| TOTAL IMPLEMENTED | $38,106 | $21,745 |
$7,270
144,527
kWh
|
$1,510
-
kW-mo/yr
|
$11,667 | $17,659 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs