Assessment Year | 1996 |
---|---|
Principal Product | Chicken fried steak, beef and chicken fajitas |
NAICS |
n/a
|
SIC | 2013: Sausages and Other Prepared Meat Products |
Sales Range | $10 M to 50M |
# of Employees | 240 |
Plant Area |
72,136
ft2
|
Annual Production | 21,000,000
lb
|
Production Hrs. Annual | 4,680
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $204,374 | 7,986,811 |
kWh
|
$0.026 |
Electricity Demand | $214,237 | 15,846 |
kW-mo/yr
|
$13.52 |
Electricity Fees | $15,083 | - |
|
- |
Natural Gas | $95,486 | 49,465 |
MMBtu
|
$1.93 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $139,979 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $103,572 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Other Liquid (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2694: Use highest temperature for chilling or cold storage | $48,359 | $50 |
$27,235
1,047,773
kWh
|
$21,124
-
kW-mo/yr
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,928 | $44,000 |
$8,490
99,355
kWh
|
$3,438
-
kW-mo/yr
|
- | - | |
03 | 2.2626: Avoid frost formation on evaporators | $12,480 | $4,500 |
$8,325
308,324
kWh
|
$4,155
-
kW-mo/yr
|
- | - | |
04 | 2.4133: Use most efficient type of electric motors | $12,393 | $35,270 |
$6,725
258,793
kWh
|
$5,668
-
kW-mo/yr
|
- | - | |
05 | 2.2626: Avoid frost formation on evaporators | $1,596 | $3,000 |
$1,596
61,547
kWh
|
- | - | - | |
06 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $906 | $2,204 |
$452
17,292
kWh
|
$454
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $629 | $314 |
$272
10,551
kWh
|
$357
-
kW-mo/yr
|
- | - | |
08 | 2.7261: Install timers and/or thermostats | $599 | $300 |
$599
23,154
kWh
|
- | - | - | |
09 | 3.4113: Treat and reuse rinse waters | $21,972 | - | - | - | - |
$21,972
-
gal
|
|
10 | 3.4113: Treat and reuse rinse waters | $23,328 | - | - | - |
$23,328
-
Tgal
|
- | |
11 | 3.4116: Meter recycled water (to reduce sewer charges) | $5,789 | - | - | - |
$5,789
-
Tgal
|
- | |
TOTAL RECOMMENDED | $139,979 | $89,638 |
$53,694
1,826,789
kWh
|
$35,196
-
kW-mo/yr
|
$29,117
-
Tgal
|
$21,972
-
gal
|
||
TOTAL IMPLEMENTED | $103,572 | $84,838 |
$44,770
1,495,311
kWh
|
$31,041
-
kW-mo/yr
|
$5,789
-
Tgal
|
$21,972
-
gal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Other Liquid (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs