Assessment Year | 2022 |
---|---|
Principal Product | Metal Stampings |
NAICS | 336370: Motor Vehicle Metal Stamping |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $100 M to 500M |
# of Employees | 680 |
Plant Area |
504,884
ft2
|
Annual Production | 22,553,512
units
|
Production Hrs. Annual | 5,840
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,594,858 | 22,601,607 |
kWh
|
$0.071 | |
Electricity Demand | $536,014 | 52,310 |
kW-mo/yr
|
$10.25 | |
Electricity Fees | $1,561 | - |
|
- | |
Natural Gas | $141,522 | 15,307 |
MMBtu
|
$9.25 | |
Waste Disposal Costs | |||||
Water Usage | $81,224 | 614,224 |
Tgal
|
$0.13 | |
TOTAL YEARLY COSTS | $2,355,179 | ||||
RECOMMENDED SAVINGS* | $52,983 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $23,961 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.6211: Conserve energy by efficient use of vending machines | $241 | - |
$186
2,616
kWh
|
$55
-
kW-mo/yr
|
- | |
02 | 2.2625: Chill water to the highest temperature possible | $24,564 | - |
$17,335
244,151
kWh
|
$7,229
-
kW-mo/yr
|
- | |
03 | 2.7224: Reduce space conditioning during non-working hours | $1,306 | $3 |
$70
978
kWh
|
- |
$1,236
-
MMBtu
|
|
04 | 2.7134: Use photocell controls | $2,682 | $248 |
$2,682
37,778
kWh
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $712 | $72 |
$712
10,030
kWh
|
- | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $14,466 | $3,681 |
$14,466
203,745
kWh
|
- | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $1,570 | $851 |
$1,210
17,035
kWh
|
$360
-
kW-mo/yr
|
- | |
08 | 2.2437: Recover waste heat from equipment | $2,345 | $2,259 |
$2,345
33,968
kWh
|
- | - | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $640 | $674 |
$640
9,018
kWh
|
- | - | |
10 | 2.2428: Use flue gases in radiant heater for space heating, ovens, etc | $4,458 | $8,975 | - | - |
$4,458
-
MMBtu
|
|
TOTAL RECOMMENDED | $52,983 | $16,763 |
$39,644
559,319
kWh
|
$7,644
-
kW-mo/yr
|
$5,694
-
MMBtu
|
||
TOTAL IMPLEMENTED | $23,961 | $7,788 |
$22,310
315,168
kWh
|
$415
-
kW-mo/yr
|
$1,236
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs