Assessment Year | 2018 |
---|---|
Principal Product | Automotive Lighting Products |
NAICS | 336320: Motor Vehicle Electrical and Electronic Equipment Manufacturing |
SIC | 3647: Vehicular Lighting Equipment |
Sales Range | greater than $500 M |
# of Employees | 1,298 |
Plant Area |
538,058
ft2
|
Annual Production | 12,140,951
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,721,283 | 45,652,132 |
kWh
|
$0.060 |
Electricity Demand | $579,946 | 94,081 |
kW-mo/yr
|
$6.16 |
Electricity Fees | $362,506 | - |
|
- |
Natural Gas | $67,040 | 33,219 |
MMBtu
|
$2.02 |
TOTAL YEARLY COSTS | $3,730,775 | |||
RECOMMENDED SAVINGS* | $108,028 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $42,173 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $8,423 | - |
$5,352
89,790
kWh
|
- |
$3,071
-
MMBtu
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,107 | $59 |
$1,758
29,484
kWh
|
$349
-
kW-mo/yr
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $19,901 | $2,251 |
$16,205
271,857
kWh
|
$3,696
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $30,301 | $51,647 |
$24,937
418,335
kWh
|
$5,364
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $1,506 | $1,246 |
$1,506
25,270
kWh
|
- | - | |
06 | 2.4133: Use most efficient type of electric motors | $1,342 | $5,885 |
$1,120
18,782
kWh
|
$222
-
kW-mo/yr
|
- | |
07 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $44,448 | $205,000 |
$9,004
151,052
kWh
|
- |
$35,444
-
MMBtu
|
|
TOTAL RECOMMENDED | $108,028 | $266,088 |
$59,882
1,004,570
kWh
|
$9,631
-
kW-mo/yr
|
$38,515
-
MMBtu
|
||
TOTAL IMPLEMENTED | $42,173 | $57,591 |
$33,167
556,391
kWh
|
$5,935
-
kW-mo/yr
|
$3,071
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs