Assessment Year 2018
Principal Product Potable Drinking Water
NAICS 221310: Water Supply and Irrigation Systems
SIC 4941: Water Supply
Sales Range $50
M
to 100
M
# of Employees 25
Plant Area 2,000,000
ft2
Annual Production 23,900,000
units
Production Hrs. Annual 8,736
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,043,580 24,549,800
kWh
Electricity Demand $866,818 47,837
kW-mo/yr
Electricity Fees $(-79,482.9) -
Natural Gas $25,786 5,846
MMBtu
TOTAL YEARLY COSTS $1,856,701
RECOMMENDED SAVINGS* $27,796 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $13,892

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.7224: Reduce space conditioning during non-working hours $1,413 - $718
16,894
kWh
- $695
-
MMBtu
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $524 $110 $524
12,335
kWh
- -
03 2.7135: Install occupancy sensors $220 $186 $220
5,147
kWh
- -
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $2,414 $5,213 $2,414
56,784
kWh
- -
05 2.4221: Install compressor air intakes in coolest locations $738 $1,819 $477
11,232
kWh
$261
-
kW-mo/yr
-
06 2.7142: Utilize higher efficiency lamps and/or ballasts $12,488 $32,763 $6,437
151,415
kWh
$6,051
-
kW-mo/yr
-
07 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air $9,339 $29,295 $585
13,755
kWh
- $8,754
-
MMBtu
08 2.2437: Recover waste heat from equipment $660 $2,876 $(-34.5)
(-811)
kWh
$(-27.2)
-
kW-mo/yr
$722
-
MMBtu
TOTAL RECOMMENDED $27,796 $72,261 $11,341
266,751
kWh
$6,285
-
kW-mo/yr
$10,170
-
MMBtu
TOTAL IMPLEMENTED $13,892 $35,935 $7,147
168,086
kWh
$6,024
-
kW-mo/yr
$722
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs