Assessment Year | 2017 |
---|---|
Principal Product | Automotive Parts |
NAICS | 332117: Powder Metallurgy Part Manufacturing |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 430 |
Plant Area |
310,200
ft2
|
Annual Production | 12,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,061,774 | 45,446,327 |
kWh
|
$0.045 |
Electricity Demand | $1,131,915 | 75,533 |
kW-mo/yr
|
$14.99 |
Electricity Fees | $18,472 | - |
|
- |
Natural Gas | $143,895 | 25,894 |
MMBtu
|
$5.56 |
TOTAL YEARLY COSTS | $3,356,056 | |||
RECOMMENDED SAVINGS* | $149,418 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $109,666 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $8,935 | $25 |
$1,155
25,435
kWh
|
- |
$7,780
-
MMBtu
|
|
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,023 | $2,041 |
$13,023
286,840
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $68,255 | $11,125 |
$41,735
919,277
kWh
|
$26,520
-
kW-mo/yr
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $17,327 | $3,124 |
$10,592
233,314
kWh
|
$6,735
-
kW-mo/yr
|
- | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,822 | $835 |
$2,337
51,480
kWh
|
$1,485
-
kW-mo/yr
|
- | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,356 | $3,070 |
$9,356
206,070
kWh
|
- | - | |
07 | 2.7135: Install occupancy sensors | $2,961 | $1,093 |
$2,961
65,226
kWh
|
- | - | |
08 | 2.2437: Recover waste heat from equipment | $13,700 | $6,580 |
$(-15.0)
(-337)
kWh
|
$(-1.5)
-
kW-mo/yr
|
$13,716
-
MMBtu
|
|
09 | 2.4322: Use or replace with energy efficient substitutes | $4,060 | $2,194 |
$4,204
92,598
kWh
|
$(-144.0)
-
kW-mo/yr
|
- | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,136 | $3,970 |
$7,136
157,186
kWh
|
- | - | |
11 | 2.4322: Use or replace with energy efficient substitutes | $843 | $1,000 |
$843
18,571
kWh
|
- | - | |
TOTAL RECOMMENDED | $149,418 | $35,057 |
$93,327
2,055,660
kWh
|
$34,595
-
kW-mo/yr
|
$21,496
-
MMBtu
|
||
TOTAL IMPLEMENTED | $109,666 | $21,324 |
$75,366
1,660,034
kWh
|
$26,520
-
kW-mo/yr
|
$7,780
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |