| Assessment Year | 1989 |
|---|---|
| Principal Product | PLASTIC DELI CONTAINERS |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 128 |
| Plant Area |
n/a
|
| Annual Production | 14,000,000
lb
|
| Production Hrs. Annual | 7,344
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $630,632 | 9,085,874 |
kWh
|
$0.069 |
| Natural Gas | $24,980 | 4,731 |
MMBtu
|
$5.28 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $15,732 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,250 | $187 |
$1,250
17,878
kWh
|
|
| 02 | 2.2511: Insulate bare equipment | $4,170 | $3,456 |
$4,170
60,082
kWh
|
|
| 03 | 2.2443: Re-use or recycle hot or cold process exhaust air | $529 | $500 |
$529
7,620
kWh
|
|
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $8,624 | $17,000 |
$8,624
124,267
kWh
|
|
| 05 | 2.4133: Use most efficient type of electric motors | $1,159 | $4,126 |
$1,159
16,706
kWh
|
|
| TOTAL RECOMMENDED | $15,732 | $25,269 |
$15,732
226,553
kWh
|
||
| TOTAL IMPLEMENTED | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs