Assessment Year | 2017 |
---|---|
Principal Product | Eggs |
NAICS | 311999: All Other Miscellaneous Food Manufacturing |
SIC | 2099: Food Preparations, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 19 |
Plant Area |
43,400
ft2
|
Annual Production | 175,219,200
units
|
Production Hrs. Annual | 4,940
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $94,023 | 1,294,776 |
kWh
|
$0.073 |
Electricity Demand | $33,035 | 3,248 |
kW-mo/yr
|
$10.17 |
Electricity Fees | $10,944 | - |
|
- |
Natural Gas | $72,586 | 11,417 |
MMBtu
|
$6.36 |
TOTAL YEARLY COSTS | $210,588 | |||
RECOMMENDED SAVINGS* | $33,418 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,065 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7229: Air condition only space necessary | $3,195 | $10 |
$3,195
44,011
kWh
|
- | - | - | - | |
02 | 2.4323: Use optimum size and capacity equipment | $1,435 | - |
$1,204
16,582
kWh
|
$231
-
kW-mo/yr
|
- | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,562 | $3 |
$1,165
16,048
kWh
|
$397
-
kW-mo/yr
|
- | - | - | |
04 | 2.7221: Lower temperature during the winter season and vice-versa | $5,220 | $120 | - | - | - |
$5,220
-
MMBtu
|
- | |
05 | 4.812: Apply for investment incentives | $1,266 | $100 | - | - | - | - | $1,266 | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $558 | $90 |
$416
5,730
kWh
|
$142
-
kW-mo/yr
|
- | - | - | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $1,505 | $580 |
$1,123
15,472
kWh
|
$382
-
kW-mo/yr
|
- | - | - | |
08 | 2.7135: Install occupancy sensors | $945 | $750 |
$945
13,018
kWh
|
- | - | - | - | |
09 | 2.3212: Optimize plant power factor | $2,569 | $1,746 | - | - | $2,569 | - | - | |
10 | 4.812: Apply for investment incentives | $6,175 | $5,000 | - | - | $6,175 | - | - | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,470 | $8,388 |
$5,573
76,767
kWh
|
$1,897
-
kW-mo/yr
|
- | - | - | |
12 | 2.4221: Install compressor air intakes in coolest locations | $394 | $871 |
$329
4,530
kWh
|
$65
-
kW-mo/yr
|
- | - | - | |
13 | 2.2511: Insulate bare equipment | $1,125 | $2,464 | - | - | - |
$1,125
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $33,418 | $20,122 |
$13,950
192,158
kWh
|
$3,113
-
kW-mo/yr
|
$8,744 |
$6,345
-
MMBtu
|
$1,266 | ||
TOTAL IMPLEMENTED | $3,065 | $843 |
$2,526
34,796
kWh
|
$539
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs