Assessment Year | 2017 |
---|---|
Principal Product | Car Batteries |
NAICS | 335912: Primary Battery Manufacturing |
SIC | 3692: Primary Batteries, Dry and Wet |
Sales Range | $100 M to 500M |
# of Employees | 130 |
Plant Area |
146,000
ft2
|
Annual Production | 5,501,414
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,242,075 | 23,611,657 |
kWh
|
$0.053 |
Electricity Demand | $448,212 | 54,846 |
kW-mo/yr
|
$8.17 |
Electricity Fees | $2,052 | - |
|
- |
Natural Gas | $193,363 | 34,560 |
MMBtu
|
$5.59 |
TOTAL YEARLY COSTS | $1,885,702 | |||
RECOMMENDED SAVINGS* | $495,598 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6211: Conserve energy by efficient use of vending machines | $1,359 | - |
$1,121
21,155
kWh
|
$238
-
kW-mo/yr
|
- | - | |
02 | 2.2531: Re-size charging openings or add movable cover or door | $1,244 | $6 | - | - |
$1,244
-
MMBtu
|
- | |
03 | 2.2621: Modify refrigeration system to operate at a lower pressure | $13,004 | $4 |
$10,730
182,224
kWh
|
$2,274
-
kW-mo/yr
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,588 | $155 |
$2,135
40,291
kWh
|
$453
-
kW-mo/yr
|
- | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $4,570 | $963 |
$4,067
76,737
kWh
|
$503
-
kW-mo/yr
|
- | - | |
06 | 2.2691: Shut off cooling if cold outside air will cool process | $5,250 | $2,002 |
$4,332
81,732
kWh
|
$918
-
kW-mo/yr
|
- | - | |
07 | 2.4224: Upgrade controls on compressors | $18,232 | $10,662 |
$18,232
344,005
kWh
|
- | - | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $989 | $804 |
$989
18,659
kWh
|
- | - | - | |
09 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $448,362 | $2,150,000 |
$876,155
16,531,225
kWh
|
$191,373
-
kW-mo/yr
|
$68,109
-
MMBtu
|
$(-687,275.0) | |
TOTAL RECOMMENDED | $495,598 | $2,164,596 |
$917,761
17,296,028
kWh
|
$195,759
-
kW-mo/yr
|
$69,353
-
MMBtu
|
$(-687,275.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs