ITAC Assessment: IP0051
ITAC logo
ITAC Assessment: IP0051
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2015
Principal Product Bottled and Canned Soft Drinks
NAICS 312111: Soft Drink Manufacturing
SIC 2086: Bottled and Canned Soft Drinks and Carbonated Waters
Sales Range $10
M
to 50
M
# of Employees 451
Plant Area 211,000
ft2
Annual Production 25,000,000
pieces
Production Hrs. Annual 8,400
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $382,531 7,373,800
kWh
Electricity Demand $174,524 15,472
kW-mo/yr
Electricity Fees $14,370 -
Natural Gas $280,507 70,163
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $39,572 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $22,902

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Water Disposal Savings
01 2.7221: Lower temperature during the winter season and vice-versa $1,391 $27 $1,017
19,596
kWh
- - $374
-
MMBtu
-
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $10,824 $161 $10,824
208,625
kWh
- - - -
03 2.4231: Reduce the pressure of compressed air to the minimum required $9,313 $261 $9,313
179,518
kWh
- - - -
04 3.5131: Recycle white water $1,246 $108 $(-35.8)
(-689)
kWh
$(-11.0)
-
kW-mo/yr
- - $1,293
-
Tgal
05 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,713 $534 $1,307
25,200
kWh
$406
-
kW-mo/yr
- - -
06 2.2437: Recover waste heat from equipment $2,349 $2,149 $(-4.2)
(-77)
kWh
- - $2,353
-
MMBtu
-
07 2.7142: Utilize higher efficiency lamps and/or ballasts $127 $255 $127
2,453
kWh
- - - -
08 2.3212: Optimize plant power factor $4,646 $12,637 - - $4,646 - -
09 2.3192: Use fossil fuel powered generator during peak demand periods $7,963 $24,900 $1,519
29,280
kWh
$8,122
-
kW-mo/yr
- $(-1,678.0)
-
MMBtu
-
TOTAL RECOMMENDED $39,572 $41,032 $24,067
463,905
kWh
$8,517
-
kW-mo/yr
$4,646 $1,049
-
MMBtu
$1,293
-
Tgal
TOTAL IMPLEMENTED $22,902 $812 $21,246
409,503
kWh
$(-11.0)
-
kW-mo/yr
- $374
-
MMBtu
$1,293
-
Tgal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Water Disposal Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs