Assessment Year 2015
Principal Product Collocation and Data Center, there is no production
NAICS 541513: Computer Facilities Management Services
SIC 7376: Computer Facilities Management Services
Sales Range $10
M
to 50
M
# of Employees 47
Plant Area 65,000
ft2
Annual Production 1
units
Production Hrs. Annual 8,760
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $523,151 19,505,250
kWh
Electricity Demand $303,598 29,561
kW-mo/yr
Electricity Fees $558,502 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $30,214 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $9,953

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
01 2.6232: Install set-back timers $9,953 - $9,953
371,425
kWh
- -
02 2.7135: Install occupancy sensors $1,501 $324 $1,501
56,009
kWh
- -
03 2.3212: Optimize plant power factor $7,258 $13,085 - - $7,258
04 2.7142: Utilize higher efficiency lamps and/or ballasts $989 $2,747 $989
36,967
kWh
- -
05 2.7313: Recycle air for heating, ventilation and air conditioning $10,513 $23,031 $8,665
323,351
kWh
$1,848
-
kW-mo/yr
-
TOTAL RECOMMENDED $30,214 $39,187 $21,108
787,752
kWh
$1,848
-
kW-mo/yr
$7,258
TOTAL IMPLEMENTED $9,953 - $9,953
371,425
kWh
- -
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs