Assessment Year | 2012 |
---|---|
Principal Product | Pharmaceutical Labels/Inserts |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
121,000
ft2
|
Annual Production | 660,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $208,177 | 3,922,460 |
kWh
|
$0.053 |
Electricity Demand | $90,931 | 8,521 |
kW-mo/yr
|
$10.67 |
Electricity Fees | $17,830 | - |
|
- |
Natural Gas | $65,273 | 3,766 |
MMBtu
|
$17.33 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $61,879 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $23,531 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,520 | - |
$2,520
94,059
kWh
|
- | - | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $980 | - |
$939
35,040
kWh
|
$41
-
kW-mo/yr
|
- | - | |
03 | 2.7135: Install occupancy sensors | $1,771 | $730 |
$1,697
63,335
kWh
|
$74
-
kW-mo/yr
|
- | - | |
04 | 2.2437: Recover waste heat from equipment | $1,847 | $1,416 | - | - |
$1,847
-
MMBtu
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $490 | $1,156 |
$470
17,520
kWh
|
$20
-
kW-mo/yr
|
- | - | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $18,261 | $92,692 |
$17,502
833,251
kWh
|
$759
-
kW-mo/yr
|
- | - | |
07 | 2.3191: Use demand controller or load shedder | $36,010 | $171,310 | - | - | - | $36,010 | |
TOTAL RECOMMENDED | $61,879 | $267,304 |
$23,128
1,043,205
kWh
|
$894
-
kW-mo/yr
|
$1,847
-
MMBtu
|
$36,010 | ||
TOTAL IMPLEMENTED | $23,531 | $93,422 |
$22,658
1,025,685
kWh
|
$873
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs