| Assessment Year | 2026 |
|---|---|
| Principal Product | Office Space |
| NAICS | 551114: Corporate, Subsidiary, and Regional Managing Offices |
| SIC | 6541: Title Abstract Offices |
| Sales Range | less than $500 k |
| # of Employees | 150 |
| Plant Area |
45,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 2,340
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $71,230 | 913,485 |
kWh
|
$0.078 |
| Electricity Demand | $21,333 | 2,045 |
kW-mo/yr
|
$10.43 |
| Electricity Fees | $8,960 | - |
|
- |
| TOTAL YEARLY COSTS | $101,523 | |||
| RECOMMENDED SAVINGS* | $54,207 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,769 | $4,586 |
$6,388
81,900
kWh
|
$4,381
-
kW-mo/yr
|
|
| 02 | 2.7493: Use double or triple glazed windows to maintain higher relative humidity and to reduce heat losses | $542 | $190 |
$231
2,956
kWh
|
$312
-
kW-mo/yr
|
|
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,347 | $5,016 |
$800
10,251
kWh
|
$548
-
kW-mo/yr
|
|
| 04 | 2.2511: Insulate bare equipment | $1,026 | $1,353 |
$609
7,810
kWh
|
$417
-
kW-mo/yr
|
|
| 05 | 2.7135: Install occupancy sensors | $1,133 | $900 |
$394
5,024
kWh
|
$739
-
kW-mo/yr
|
|
| 06 | 2.7261: Install timers and/or thermostats | $7,519 | $2,774 |
$540
6,922
kWh
|
$6,979
-
kW-mo/yr
|
|
| 07 | 2.9114: Use solar heat to make electricty | $20,676 | $94,017 |
$11,882
152,330
kWh
|
$8,794
-
kW-mo/yr
|
|
| 08 | 2.4133: Use most efficient type of electric motors | $6,761 | $4,672 |
$5,714
73,260
kWh
|
$1,047
-
kW-mo/yr
|
|
| 09 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $4,434 | $3,000 |
$4,434
56,840
kWh
|
- | |
| TOTAL RECOMMENDED | $54,207 | $116,506 |
$30,990
397,292
kWh
|
$23,216
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs