Assessment Year | 2024 |
---|---|
Principal Product | Museum and Office Space |
NAICS | 712110: Museums |
SIC | 8412: Museums and Art Galleries |
Sales Range | less than $500 k |
# of Employees | 10 |
Plant Area |
43,560
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 1,664
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $17,254 | 152,692 |
kWh
|
$0.11 | |
Waste Disposal Costs | |||||
Water Usage | $2,153 | 474 |
Tgal
|
$4.54 | |
TOTAL YEARLY COSTS | $19,407 | ||||
RECOMMENDED SAVINGS* | $1,819 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $631 | - |
$631
5,599
kWh
|
|
02 | 2.7212: Install or upgrade insulation on hvac distribution systems | $384 | $1,537 |
$384
3,402
kWh
|
|
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $35 | $70 |
$35
306
kWh
|
|
04 | 2.7135: Install occupancy sensors | $49 | $257 |
$49
432
kWh
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $334 | $356 |
$334
2,962
kWh
|
|
06 | 2.7444: Close holes and openings in building such as broken windows | $121 | $73 |
$121
1,071
kWh
|
|
07 | 2.3191: Use demand controller or load shedder | $266 | $1,358 |
$266
2,358
kWh
|
|
TOTAL RECOMMENDED | $1,819 | $3,651 |
$1,819
16,131
kWh
|
||
TOTAL IMPLEMENTED | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs