| Assessment Year | 2023 |
|---|---|
| Principal Product | Office Space |
| NAICS | 551114: Corporate, Subsidiary, and Regional Managing Offices |
| SIC | 6541: Title Abstract Offices |
| Sales Range | less than $500 k |
| # of Employees | 80 |
| Plant Area |
68,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 2,548
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $46,955 | 579,992 |
kWh
|
$0.081 |
| Electricity Demand | $10,567 | 1,320 |
kW-mo/yr
|
$8.01 |
| Electricity Fees | $10,139 | - |
|
- |
| Natural Gas | $114,477 | 11,156 |
MMBtu
|
$10.26 |
| TOTAL YEARLY COSTS | $182,138 | |||
| RECOMMENDED SAVINGS* | $173,937 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,362 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,774 | $1,526 |
$2,194
27,429
kWh
|
$580
-
kW-mo/yr
|
- | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $137 | $78 |
$137
1,712
kWh
|
- | - | - | |
| 03 | 4.231: Purchase equipment instead of leasing | $77,000 | $112,794 | - | - | - | $77,000 | |
| 04 | 2.9114: Use solar heat to make electricty | $86,169 | $883,093 |
$75,756
946,954
kWh
|
$10,413
-
kW-mo/yr
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,633 | $4,136 |
$3,431
42,874
kWh
|
$1,202
-
kW-mo/yr
|
- | - | |
| 06 | 2.2136: Install / repair insulation on steam lines | $592 | $496 | - | - |
$592
-
MMBtu
|
- | |
| 07 | 2.7494: Install storm windows and doors | $2,632 | $32,631 |
$182
2,269
kWh
|
- |
$2,450
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $173,937 | $1,034,754 |
$81,700
1,021,237
kWh
|
$12,195
-
kW-mo/yr
|
$3,042
-
MMBtu
|
$77,000 | ||
| TOTAL IMPLEMENTED | $5,362 | $4,710 |
$3,568
44,586
kWh
|
$1,202
-
kW-mo/yr
|
$592
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs