Assessment Year | 2023 |
---|---|
Principal Product | Office Space |
NAICS | 551114: Corporate, Subsidiary, and Regional Managing Offices |
SIC | 6541: Title Abstract Offices |
Sales Range | less than $500 k |
# of Employees | 50 |
Plant Area |
40,560
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 2,574
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $42,618 | 463,200 |
kWh
|
$0.092 |
Electricity Demand | $18,934 | 1,493 |
kW-mo/yr
|
$12.68 |
Electricity Fees | $8,982 | - |
|
- |
Natural Gas | $14,146 | 1,659 |
MMBtu
|
$8.53 |
TOTAL YEARLY COSTS | $84,680 | |||
RECOMMENDED SAVINGS* | $69,808 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,190 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7241: Install outside air damper / economizer on hvac unit | $24,563 | $10,218 |
$14,953
162,535
kWh
|
$9,610
-
kW-mo/yr
|
- | |
02 | 2.9114: Use solar heat to make electricty | $26,775 | $203,319 |
$22,463
244,168
kWh
|
$4,312
-
kW-mo/yr
|
- | |
03 | 3.1161: Eliminate/reduce an operation | $5,835 | - |
$3,552
38,610
kWh
|
$2,283
-
kW-mo/yr
|
- | |
04 | 2.6231: Utilize controls to operate equipment only when needed | $796 | - | - | - |
$796
-
MMBtu
|
|
05 | 2.7494: Install storm windows and doors | $619 | $7,463 |
$50
542
kWh
|
$85
-
kW-mo/yr
|
$485
-
MMBtu
|
|
06 | 2.7135: Install occupancy sensors | $306 | $388 |
$184
2,005
kWh
|
$121
-
kW-mo/yr
|
- | |
07 | 2.6218: Turn off equipment when not in use | $254 | - |
$71
772
kWh
|
$183
-
kW-mo/yr
|
- | |
08 | 2.7226: Use computer programs to optimize hvac performance | $4,154 | $4,776 |
$3,826
41,586
kWh
|
$328
-
kW-mo/yr
|
- | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,267 | - |
$2,598
28,237
kWh
|
$1,670
-
kW-mo/yr
|
- | |
10 | 2.1224: Replace boiler | $2,240 | $49,894 | - | - |
$2,240
-
MMBtu
|
|
TOTAL RECOMMENDED | $69,808 | $276,058 |
$47,698
518,455
kWh
|
$18,590
-
kW-mo/yr
|
$3,520
-
MMBtu
|
||
TOTAL IMPLEMENTED | $7,190 | $388 |
$3,808
41,387
kWh
|
$2,587
-
kW-mo/yr
|
$796
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |