Assessment Year | 2020 |
---|---|
Principal Product | Bottled Water Manufacturing |
NAICS | 312112: Bottled Water Manufacturing |
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $10 M to 50M |
# of Employees | 35 |
Plant Area |
200,000
ft2
|
Annual Production | 205,000,000
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $473,357 | 6,762,240 |
kWh
|
$0.070 |
Electricity Demand | $191,969 | 15,053 |
kW-mo/yr
|
$12.75 |
Electricity Fees | $54,493 | - |
|
- |
Natural Gas | $2,242 | 294 |
MMBtu
|
$7.62 |
TOTAL YEARLY COSTS | $722,061 | |||
RECOMMENDED SAVINGS* | $59,013 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $46,952 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $15,040 | $26,145 | - |
$15,040
-
kW-mo/yr
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $21,285 | $6,673 |
$16,619
237,409
kWh
|
$4,667
-
kW-mo/yr
|
|
03 | 2.4226: Use / purchase optimum sized compressor | $5,211 | $50,440 |
$3,500
50,000
kWh
|
$1,711
-
kW-mo/yr
|
|
04 | 2.4221: Install compressor air intakes in coolest locations | $12,061 | $2,400 |
$12,061
172,298
kWh
|
- | |
05 | 2.3132: Recharge batteries on during off-peak demand periods | $5,416 | - | - |
$5,416
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $59,013 | $85,658 |
$32,179
459,707
kWh
|
$26,833
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $46,952 | $83,258 |
$20,119
287,409
kWh
|
$26,833
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs