Assessment Year | 2019 |
---|---|
Principal Product | Steel Processing and Pickling of Master Coils |
NAICS | 423510: Metal Service Centers and Other Metal Merchant Wholesalers |
SIC | 5051: Metals Service Centers and Offices |
Sales Range | $100 M to 500M |
# of Employees | 200 |
Plant Area |
500,000
ft2
|
Annual Production | 1,000,000
ton
|
Production Hrs. Annual | 6,200
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $545,342 | 9,089,040 |
kWh
|
$0.060 |
Electricity Demand | $359,494 | 28,284 |
kW-mo/yr
|
$12.71 |
Natural Gas | $334,474 | 68,680 |
MMBtu
|
$4.87 |
TOTAL YEARLY COSTS | $1,239,310 | |||
RECOMMENDED SAVINGS* | $113,980 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $49,118 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2414: Use waste heat from hot flue gases to preheat | $33,543 | $6,600 | - | - |
$33,543
-
MMBtu
|
|
02 | 2.4221: Install compressor air intakes in coolest locations | $2,588 | $1,928 |
$1,203
20,055
kWh
|
$1,385
-
kW-mo/yr
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,925 | $300 |
$1,713
27,415
kWh
|
$1,212
-
kW-mo/yr
|
- | |
04 | 2.4133: Use most efficient type of electric motors | $62,274 | $210,000 |
$62,274
1,037,905
kWh
|
- | - | |
05 | 3.6123: Burn wood by-products for heat | $5,683 | $15,144 | - | - |
$5,683
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,967 | $7,769 |
$1,971
32,853
kWh
|
$4,996
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $113,980 | $241,741 |
$67,161
1,118,228
kWh
|
$7,592
-
kW-mo/yr
|
$39,226
-
MMBtu
|
||
TOTAL IMPLEMENTED | $49,118 | $29,813 |
$3,684
60,268
kWh
|
$6,207
-
kW-mo/yr
|
$39,226
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs