| Assessment Year | 2017 |
|---|---|
| Principal Product | Wastewater Treatment Facility |
| NAICS | 221320: Sewage Treatment Facilities |
| SIC | 4952: Sewerage Systems |
| Sales Range | less than $500 k |
| # of Employees | 84 |
| Plant Area |
200,000
ft2
|
| Annual Production | 24,687,728
lb
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,366,236 | 20,984,569 |
kWh
|
$0.065 |
| Electricity Demand | $33,098 | 3,102 |
kW-mo/yr
|
$10.67 |
| Electricity Fees | $0.1 | - |
|
- |
| Natural Gas | $146,138 | 21,100 |
MMBtu
|
$6.93 |
| TOTAL YEARLY COSTS | $1,545,472 | |||
| RECOMMENDED SAVINGS* | $139,874 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $84,038 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $79,158 | $193,800 |
$66,994
788,171
kWh
|
$12,164
-
kW-mo/yr
|
|
| 02 | 2.9114: Use solar heat to make electricty | $53,319 | $1,029,975 |
$53,319
627,283
kWh
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,932 | $14,716 |
$2,280
26,832
kWh
|
$1,652
-
kW-mo/yr
|
|
| 04 | 2.4224: Upgrade controls on compressors | $2,517 | $7,106 |
$2,517
29,603
kWh
|
- | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $948 | $1,847 |
$551
6,448
kWh
|
$397
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $139,874 | $1,247,444 |
$125,661
1,478,337
kWh
|
$14,213
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $84,038 | $210,363 |
$69,825
821,451
kWh
|
$14,213
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs