Assessment Year 2009
Principal Product Sterile Water
NAICS 423450: Medical, Dental, and Hospital Equipment and Supplies Merchant Wholesalers
SIC 5047: Medical, Dental, and Hospital Equipment and Supplies
Sales Range $5
M
to 10
M
# of Employees 100
Plant Area 91,800
ft2
Annual Production 66,000,000
pieces
Production Hrs. Annual 8,520
hrs
Location (State) Illinois

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $361,278 5,008,052
kWh
Electricity Demand $50,792 9,459
kW-mo/yr
Natural Gas $201,684 20,626
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $21,720 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $14,318

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings Personnel Changes Savings Primary Raw Material Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $6,950 $19,296 $5,876
81,632
kWh
$1,006
-
kW-mo/yr
- - $(-39.0) $107
02 2.7142: Utilize higher efficiency lamps and/or ballasts $1,522 $458 $313
4,352
kWh
$32
-
kW-mo/yr
- - $440 $737
03 2.1233: Analyze flue gas for proper air/fuel ratio $7,193 - - - $7,193
-
MMBtu
- - -
04 2.2135: Repair and eliminate steam leaks $875 $400 - - $830
-
MMBtu
$45
-
Tgal
- -
05 2.2136: Install / repair insulation on steam lines $1,524 $1,260 - - $1,524
-
MMBtu
- - -
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $137 $115 $137
1,907
kWh
- - - - -
07 2.4224: Upgrade controls on compressors $3,067 $8,134 $3,067
42,600
kWh
- - - - -
08 2.6211: Conserve energy by efficient use of vending machines $452 - $259
3,600
kWh
$193
-
kW-mo/yr
- - - -
TOTAL RECOMMENDED $21,720 $29,663 $9,652
134,091
kWh
$1,231
-
kW-mo/yr
$9,547
-
MMBtu
$45
-
Tgal
$401 $844
TOTAL IMPLEMENTED $14,318 $10,367 $3,517
48,859
kWh
$32
-
kW-mo/yr
$9,547
-
MMBtu
$45
-
Tgal
$440 $737
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings Personnel Changes Savings Primary Raw Material Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs