Assessment Year | 2008 |
---|---|
Principal Product | Automotive Parts Finisher |
NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
Sales Range | $1 M to 5M |
# of Employees | 20 |
Plant Area |
30,000
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 2,060
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $56,201 | 687,292 |
kWh
|
$0.082 |
Electricity Demand | $20,375 | 4,066 |
kW-mo/yr
|
$5.01 |
Electricity Fees | $1,387 | - |
|
- |
Natural Gas | $10,883 | 1,061 |
MMBtu
|
$10.26 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,707 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,223 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4224: Upgrade controls on compressors | $4,809 | $5,020 |
$3,547
43,260
kWh
|
$1,262
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,810 | $2,300 |
$3,547
43,260
kWh
|
$1,263
-
kW-mo/yr
|
- | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $218 | - |
$218
2,658
kWh
|
- | - | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $3,150 | $1,080 |
$3,150
38,419
kWh
|
- | - | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $4,037 | $1,404 |
$4,037
49,230
kWh
|
- | - | - | |
06 | 2.7135: Install occupancy sensors | $922 | $2,977 |
$682
8,313
kWh
|
$240
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $109 | $89 |
$39
480
kWh
|
$15
-
kW-mo/yr
|
$60 | $(-5.0) | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $382 | $833 |
$292
3,565
kWh
|
$25
-
kW-mo/yr
|
$21 | $44 | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $270 | - |
$150
1,800
kWh
|
$120
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $18,707 | $13,703 |
$15,662
190,985
kWh
|
$2,925
-
kW-mo/yr
|
$81 | $39 | ||
TOTAL IMPLEMENTED | $6,223 | $6,199 |
$4,560
55,618
kWh
|
$1,543
-
kW-mo/yr
|
$81 | $39 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs