Assessment Year | 2001 |
---|---|
Principal Product | Custom Compound Resins |
NAICS |
n/a
|
SIC | 3087: Custom Compounding of Purchased Plastics Resins |
Sales Range | $10 M to 50M |
# of Employees | 99 |
Plant Area |
46,000
ft2
|
Annual Production | 30,000,000
lb
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $72,385 | 2,162,820 |
kWh
|
$0.033 |
Electricity Demand | $65,378 | 5,342 |
kW-mo/yr
|
$12.24 |
Electricity Fees | $9,581 | - |
|
- |
Natural Gas | $74,217 | 10,018 |
MMBtu
|
$7.41 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $89,329 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,027 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,871 | $1,200 |
$1,084
32,825
kWh
|
$787
-
kW-mo/yr
|
- | - | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $418 | - |
$242
7,343
kWh
|
$176
-
kW-mo/yr
|
- | - | - | |
03 | 2.4133: Use most efficient type of electric motors | $5,738 | $12,553 |
$316
9,561
kWh
|
$5,422
-
kW-mo/yr
|
- | - | - | |
04 | 2.7135: Install occupancy sensors | $2,513 | $4,800 |
$495
15,009
kWh
|
$2,018
-
kW-mo/yr
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $374 | $1,462 |
$78
2,366
kWh
|
$40
-
kW-mo/yr
|
$193 | - | $63 | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,715 | $82,109 | n/a |
$5,173
156,756
kWh
|
$4,542
-
kW-mo/yr
|
- | - | - |
07 | 4.426: Modify workload | $68,700 | $7,200 | - | - | $50,700 | $18,000 | - | |
TOTAL RECOMMENDED | $89,329 | $109,324 |
$7,388
223,860
kWh
|
$12,985
-
kW-mo/yr
|
$50,893 | $18,000 | $63 | ||
TOTAL IMPLEMENTED | $8,027 | $13,753 |
$1,642
49,729
kWh
|
$6,385
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs