| Assessment Year | 2016 |
|---|---|
| Principal Product | baby care products |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 200 |
| Plant Area |
298,160
ft2
|
| Annual Production | 250,000,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $526,499 | 8,516,800 |
kWh
|
$0.062 |
| Electricity Demand | $229,868 | 18,576 |
kW-mo/yr
|
$12.37 |
| Natural Gas | $34,517 | 5,136 |
MMBtu
|
$6.72 |
| TOTAL YEARLY COSTS | $790,884 | |||
| RECOMMENDED SAVINGS* | $68,763 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $43,409 | $75,175 |
$29,163
486,023
kWh
|
$14,246
-
kW-mo/yr
|
|
| 02 | 2.4226: Use / purchase optimum sized compressor | $8,956 | $7,888 |
$5,953
99,220
kWh
|
$3,003
-
kW-mo/yr
|
|
| 03 | 2.4221: Install compressor air intakes in coolest locations | $11,535 | $1,320 |
$8,240
137,327
kWh
|
$3,295
-
kW-mo/yr
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,604 | $8,596 |
$2,303
38,369
kWh
|
$1,301
-
kW-mo/yr
|
|
| 05 | 2.2696: Use excess cold process fluid for industrial cooling needs | $1,259 | $500 |
$487
8,112
kWh
|
$772
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $68,763 | $93,479 |
$46,146
769,051
kWh
|
$22,617
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs