| Assessment Year | 2014 |
|---|---|
| Principal Product | Machined Parts |
| NAICS | 332439: Other Metal Container Manufacturing |
| SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 300 |
| Plant Area |
120,000
ft2
|
| Annual Production | 12,000,000
lb
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Iowa |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $227,549 | 4,757,952 |
kWh
|
$0.048 |
| Electricity Demand | $56,391 | 7,961 |
kW-mo/yr
|
$7.08 |
| Electricity Fees | $12,740 | - |
|
- |
| Natural Gas | $59,609 | 9,288 |
MMBtu
|
$6.42 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $28,165 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4239: Eliminate or reduce compressed air usage | $12,860 | $845 |
$10,685
223,383
kWh
|
$2,175
-
kW-mo/yr
|
- | |
| 02 | 2.4239: Eliminate or reduce compressed air usage | $2,840 | $1,090 |
$2,840
59,405
kWh
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,290 | $27,423 |
$7,717
161,442
kWh
|
$1,573
-
kW-mo/yr
|
- | |
| 04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,757 | $460 | - | - |
$1,757
-
MMBtu
|
|
| 05 | 2.7135: Install occupancy sensors | $571 | $1,430 |
$571
11,945
kWh
|
- | - | |
| 06 | 2.7442: Keep doors and windows shut when not on use | $847 | $4,000 | - | - |
$847
-
MMBtu
|
|
| TOTAL RECOMMENDED | $28,165 | $35,248 |
$21,813
456,175
kWh
|
$3,748
-
kW-mo/yr
|
$2,604
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs